MKP-AL / MKP-ALO Aluminum Can AC Filter Capacitor — Direct Manufacturer

Cylindrical aluminum AC output filter and power factor correction capacitor (300V–690V AC, 10µF–300µF dry or 5–30 Kvar oil-filled) for PV/wind inverters, UPS, and VFDs.

SMILER MKP-AL cylindrical aluminum can AC output filter film capacitor

Verified Electrical & Mechanical Specifications

Dry-Type (MKP-AL)
300V–450V AC (up to 1400VAC custom), 10µF–300µF, up to 20kHz
Oil-Filled (MKP-ALO)
300V–690V AC, 5–30 Kvar (99.5–597.1µF), Overpressure Disconnector
Tolerance
±5% (J), ±10% (K)
Climatic Category
40/85/56 (-40°C to +85°C), Altitude ≤ 2,000m
Life Expectancy
100,000 hours at Un, θhs = 70°C
Dissipation Factor
tan δ ≤ 0.001 (MKP-ALO) / ≤ 2×10⁻³ @ 100Hz (MKP-AL)
Dielectric Test
1.5Un 10s (MKP-AL) / 2.15Un 5s (MKP-ALO)
Reference Standards
IEC 61071, GB/T 17702, GB/T 12747.1/2-2017
Request a Quote for MKP-AL / ALO Back to All Series

Product Overview & Dielectric Architecture

MKP-AL / ALO is a metallized polypropylene film capacitor family built into aluminum cans for AC filtering duty. The MKP-AL dry version covers 300V–450V AC (custom up to 1400V AC) with 10µF–300µF and ripple capability to 20kHz. The MKP-ALO oil-filled version spans 300V–690V AC at 5–30 Kvar (99.5–597.1µF) and adds an overpressure disconnector for safe end-of-life behavior. Both share ±5% (J) or ±10% (K) tolerance and a 40/85/56 climatic category rated from -40°C to +85°C at altitudes up to 2,000m.

These capacitors sit on the AC side of grid-tied solar and wind inverter outputs, three-phase UPS filtering, industrial VFD harmonic suppression, and low-voltage reactive power compensation. The self-healing metallized film construction tolerates transient overvoltage and surge current that would degrade electrolytics. Life expectancy reaches 100,000 hours at Un with θhs = 70°C, so the family suits cabinets expected to run for a decade or more without capacitor replacement.

Electrical Behavior & Compliance Standards

Electrically, MKP-AL / ALO behaves as a low-loss AC filter element. Dissipation factor stays at tan δ ≤ 0.001 for the oil-filled MKP-ALO and ≤ 2×10⁻³ at 100Hz for the dry MKP-AL, keeping internal heating modest under continuous harmonic current. The dry design handles switching ripple to 20kHz, which matches PWM inverter output spectra. Dielectric proof testing runs at 1.5Un for 10s on MKP-AL and 2.15Un for 5s on MKP-ALO, giving OEMs margin against line surges and commutation spikes.

Thermal and safety design centers on the aluminum can, which spreads heat from the film winding and holds internal pressure. The MKP-ALO overpressure disconnector opens the internal path if a fault raises pressure, isolating the capacitor before the can ruptures. Self-healing film clears local breakdowns and keeps capacitance stable over service life. The series is referenced to IEC 61071 and GB/T 17702 for the dry type, and GB/T 12747.1/2-2017 for the oil-filled power-factor type, so designers can map test and derating practice to familiar standards.

Circuit Selection & Typical Applications

Sizing MKP-AL / ALO starts with the AC voltage and harmonic spectrum at the mounting point, not just the nominal line voltage. Engineers then pick dry or oil-filled construction, capacitance, and can size to keep case temperature within the 40/85/56 envelope.

  • Choose MKP-AL dry-type for inverter output filters and UPS AC stages where ripple reaches 20kHz and 300V–450V AC fits; specify the 1400V AC custom option only after confirming insulation coordination.
  • Choose MKP-ALO oil-filled units for low-voltage PFC banks at 300V–690V AC and 5–30 Kvar, where the overpressure disconnector and tan δ ≤ 0.001 support continuous reactive duty.
  • Verify RMS current against the harmonic load, then check that expected hot-spot temperature stays at or below 70°C to preserve the 100,000-hour life rating.
  • Confirm can diameter, terminal style, and mounting clearance inside the cabinet, and account for altitude derating above 2,000m.
  • State tolerance class J or K and request the dielectric test report at 1.5Un or 2.15Un to match your incoming inspection plan.
  • Grid-Tied Solar & Wind Inverter Output Filters
  • Three-Phase UPS AC Filtering
  • Industrial VFD Harmonic Suppression
  • Low-Voltage Reactive Power Compensation (PFC)

OEM Manufacturing & Quality Screening

SMILER builds MKP-AL / ALO in its Foshan Shunde facility, where nine automated lines and a dedicated QA/QC team support volume production. Every unit passes electrical screening, including AC/DC empowerment and DC withstand voltage testing, plus leak inspection before packing. Finished-product qualification runs at ≥99.93%, which matters for OEMs placing these capacitors on inverter and UPS assemblies with long field warranties.

Prototyping moves quickly: the shortest sample lead time is 5 days, and average mass production delivery is 15 days. OEM customization covers capacitance, voltage rating, can dimensions, terminal configuration, and private-label marking. Buyers integrating MKP-AL / ALO into a new inverter platform can request application-specific ratings and test documentation early, then lock the specification before the pilot build.

Explore related industrial applications, browse our engineering selection guides, or request a MKP-AL / ALO datasheet and sample quote.

MKP-AL / ALO Frequently Asked Questions

When should I specify MKP-AL dry-type instead of MKP-ALO oil-filled?

Pick MKP-AL for 300V–450V AC inverter output and UPS filter stages with ripple to 20kHz, where 10µF–300µF fits. Pick MKP-ALO for 300V–690V AC reactive power compensation at 5–30 Kvar, where the oil-filled design, tan δ ≤ 0.001, and overpressure disconnector suit continuous PFC duty.

What dielectric and safety tests does MKP-AL / ALO carry?

MKP-AL is dielectric tested at 1.5Un for 10s and MKP-ALO at 2.15Un for 5s. The series references IEC 61071 and GB/T 17702 for the dry type, and GB/T 12747.1/2-2017 for the oil-filled type. MKP-ALO also includes an overpressure disconnector for controlled failure.

How do I estimate service life for MKP-AL / ALO in a hot cabinet?

The rated life is 100,000 hours at Un with hot-spot temperature θhs = 70°C under the 40/85/56 climatic category. Keep measured case and hot-spot temperatures at or below that point, and derate for altitude above 2,000m. Share your thermal data with SMILER for a rating check.

Need Datasheets or Custom OEM Film Capacitors?

Send your capacitance, voltage rating, and mechanical drawing. Our 9-member engineering team replies within 24 hours with 5-day prototyping availability.

Request a Quote